Oil cooler, Remote start/stop controls – Carrier 17/19EX User Manual

Page 86

Advertising
background image

Oil Cooler

The oil must be cooled when the compressor is running.

EX Compressors: This is accomplished through a small, plate-type heat exchanger. The heat

exchanger uses liquid condenser refrigerant as the cooling liquid. A refrigerant thermostatic

expansion valve (TXV) regulates refrigerant flow to control oil temperature entering the

bearings. There is always a flow of refrigerant bypassing the TXV. The bulb for the expansion

valve is strapped to the oil supply line leaving the heat exchanger and the valve is set to

maintain 110 F (43 C).

Note: The expansion valve is not adjustable. Oil sump temperature may be at a lower tempera-

ture.

FA Compressors: The oil cooler is a water cooled, tube-in-shell type heat exchanger. A plug

valve is manually set to maintain proper temperatures. Set the valve to maintain 145 F (63 C) oil

sump temperatures while the compressor is running.

Remote Start/Stop Controls

A remote device, such as a timeclock which uses a set of contacts, may be used to start and

stop the machine. However, the device should not be programmed to start and stop the

machine in excess of 2 or 3 times every 12 hours. If more than 8 starts in 12 hours occur, then

an Excessive Starts alarm is displayed, preventing the machine from starting. The operator

must reset the alarm at the LID in order to override the starts counter and start the machine. If

Advertising