Example 6 — Lead/Lag Configuration Display Screen

To access this display from the LID default screen:

1. Press MENU.

2. Press SERVICE.

3. Scroll down to highlight EQUIPMENT CONFIGURATION.

4. Press SELECT.

5. Scroll down to highlight Lead/Lag.

6. Press SELECT.

Table 2, Example 6 — Lead/Lag Configuration Screen

Description

Configurable
Range

Units

Reference
Point Name

Default
Value

LEAD/LAG SELECT

DISABLE =0, LEAD =1,
LAG =2, STANDBY =3

Load Balance Option
Common Sensor Option
LAG Percent Capacity
LAG Address
LAG START Timer
LAG STOP Timer
PRESTART FAULT Timer
STANDBY Chiller Option
STANDBY Percent Capacity
STANDBY Address

0-3

DISABLE/ENABLE
DISABLE/ENABLE
25-75
1-236
2-60
2-60
0-30
DISABLE/ENABLE
25-75
1-236

%

MIN
MIN
MIN

%

leadlag

loadbal
commsens
lag per
lag add
lagstart
lagstop
preflt
stndopt
stnd per
stnd add

0

DISABLE
DISABLE
50
92
10
10

1

5

DISABLE
50
93