F. start-up failures, Click here for table 8f — start-up failures – Carrier 17/19EX User Manual

Page 315

Advertising
background image

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
F. Start-Up Failures:

This is an alarm condition. A manual reset is required to clear.

Primary
Message

Secondary
Message

Alarm Message/Primary
Cause

Additional Cause/Remedy

Failure To
Start

Low Oil Pressure

OILPD [VALUE] exceeded limit
of [LIMIT]*. Check oil pump sys-
tem.

Check for closed oil supply valves.
Check oil filter. Check for low oil tem-
perature. Check transducer accuracy.

Failure To
Start

Oil Press Sensor
Fault

OILPD [VALUE] exceeded limit
of [LIMIT]*. Check oil pressure
sensor.

Check for excessive refrigerant in oil
sump. Run oil pump manually for 5 min-
utes. For hermetic compressors, check
both oil pressure and cooler pressure.
For open-drive units, check calibration
of oil pressure differential amplifier
modules. Check wiring. Replace trans-
ducers if necessary.

Failure To
Start

Low Chilled
Water Flow

EVFL Evap Flow Fault: Check
water pump/flow switch.

Check wiring to flow switch. Check
through Control Test for proper switch
operation.

Failure To
Start

Low Condenser
Water Flow

CDFL Cond. Flow Fault: Check
water pump/flow switch.

Check wiring to flow switch. Check
through Control Test for proper switch
operation.

Failure To
Start

Starter Fault

STR FLT Starter Fault: Check
starter for Fault Source.

A starter protective device has faulted.
Check starter for ground fault, voltage
trip, temperature trip, etc.

Failure To
Start

Starter Overload
Trip

STR FLT Starter Overload Trip:
Check amps calibration/reset
overload.

Reset overloads, check ICR relay
before restarting machine.

Failure To
Start

Line Voltage
Dropout

V P Single-Cycle Dropout
Detected: Check voltage supply.

Check voltage supply. Check trans-
formers for supply. Check with utility if
voltage supply is erratic. Monitor must
be installed to confirm consistent,
single-cycle dropouts. Check low oil
pressure switch.

Failure To
Start

High Condenser
Pressure

High Condenser Pressure
[LIMIT]:* Check switch 2C aux,
and water temperature/flow.

Check for proper design condenser flow
and temperature. Check condenser
approach. Check 2C auxiliary contacts
on oil sump starter. Check high pres-
sure switch.

Failure To
Start

Excess Accelera-
tion Time

CA P Excess Acceleration:
Check guide vane closure at
start-up.

Check that guide vanes are closed at
start-up. Check starter for proper opera-
tion. Reduce unit pressure if possible.