To prevent accidental start-up – Carrier 17/19EX User Manual

Page 176

Advertising
background image

RLA by manually overriding the guide vane target value on the LID and setting the chilled

water set point to a low value. Do not exceed 105% of the nameplate RLA.

3. When a steady motor current value in the desired range is met, compare the compressor

motor amps value on the Status01 screen to the actual amps shown on the ammeter on the

starter. Adjust the amps value on the LID to the actual value seen at the starter if there is a

difference. Highlight the amps value then press SELECT. Press INCREASE or DECREASE

to bring the value to that indicated on the ammeter. Press ENTER when equal.

4. Make sure that the target guide vane position is released into AUTOMATIC mode.

To Prevent Accidental Start-Up

The PIC can be set up so that start-up of the unit is more difficult than just pressing the

LOCAL or CCN softkeys during machine service or when necessary. By accessing the

Status01 screen, and highlighting the chiller Start/Stop line, the value can be overridden to stop

by pressing SELECT and then the STOP and ENTER softkeys. ‘‘SUPVSR’’ will appear after the

value. When attempting to restart, remember to release the override. The default machine

message line will also state that the Start/Stop has been set to ‘‘Start’’ or ‘‘Stop’’ when the value

is overridden.