Condenser – Carrier 17/19EX User Manual

Page 247

Advertising
background image

Condenser

Since this water circuit is usually an open-type system, the tubes may be subject to

contamination and scale. Clean the condenser tubes with a rotary tube cleaning system at least

once per year, and more often if the water is contaminated. Inspect the entering and leaving

condenser water sensors for signs of slime, corrosion, or scale. Replace the sensor if corroded

or remove any scale if found.

Higher than normal condenser pressures, together with the inability to reach full refrigeration

load, usually indicate dirty tubes or air in the machine. If the refrigeration log indicates a rise

above normal condenser pressures, check the condenser refrigerant temperature against the

leaving condenser water temperature. If this reading is more than what the design difference is

supposed to be, then the condenser tubes may be dirty, or water flow may be incorrect.

Because HFC134-a is a high-pressure refrigerant, air usually does not enter the machine,

rather, the refrigerant leaks out.

During the tube cleaning process, use brushes especially designed to avoid scraping and

scratching the tube wall. Contact your Carrier representative to obtain these brushes.

Do not

use wire brushes.

Advertising