To View and Change Set Points (

Figure 20

)

1. To view the Set Point table, at the Menu screen press SETPOINT.

2. There are 4 set points on this screen: Base Demand Limit; LCW Set Point (leaving chilled

water set point); ECW Set Point (entering chilled water set point); and ICE BUILD set point.

Only one of the chilled water set points can be active at one time, and the type of set point

is activated in the Service menu. ICE BUILD is also activated and configured in the Service

menu.

3. Press NEXT or PREVIOUS to highlight the desired set point entry.

STATUS

SCHEDULE

SETPOINT

SERVICE

NEXT

PREVIOUS

SELECT

EXIT