Machine communication wiring, Lead/lag operation – Carrier 17/19EX User Manual

Page 98

Advertising
background image

Machine Communication Wiring

Refer to the machine’s Installation Instructions and

Carrier Comfort Network Interface

section

for information on machine communication wiring.

Lead/Lag Operation

The PIC control provides the ability to operate 2 chillers in the LEAD/LAG mode. It also

provides the additional ability to start a designated standby chiller when either the lead or lag

chiller is faulted and capacity requirements are not met. The lead/lag option operates in CCN

mode only. If any other chiller configured for lead/lag is set to the LOCAL or OFF modes, it will

be unavailable for lead/lag operation.

Note: Lead/lag configuration is viewed and edited in Lead/Lag, under the Equipment Configu-

ration table of the Service menu. Lead/lag status during machine operation is viewed in

the MAINT04 table in the Control Algorithm Status table.

Lead/Lag Chiller Configuration and Operation

The configured lead chiller is identified when the LEAD/LAG SELECT value for that chiller is

configured to the value of ‘‘1.’’ The configured lag chiller is identified when the LEAD/LAG

SELECT for that chiller is configured to the value of ‘‘2.’’ The standby chiller is configured to a

value of ‘‘3.’’ A value of ‘‘0’’ disables the lead/lag in that chiller.

To configure the LAG ADDRESS value on the LEAD/LAG Configuration table, always use

the address of the other chiller on the system for this value. Using this address will make it

easier to rotate the lead and lag machines.