8. Press RELEASE to automate the chiller start/stop value on the Status01 screen to enable

the chiller to start. The initial factory setting of this value is overridden to stop in order to

prevent accidental start-up.

Manual Operation of the Guide Vanes

Manual operation of the guide vanes is helpful to establish a steady motor current for

calibration of the motor amps value.

In order to manually operate the guide vanes, it is necessary to override the

TARGET GUIDE

VANE POSITION

value which is accessed on the Status01 screen. Manual control is indicated

by the word ‘‘SUPVSR!’’ flashing after the target value position. Manual control is also indicated

on the default screen on the run status line.

1. Access the Status01 screen and look at the target guide vane position (

Figure 18

). If the

compressor is off, the value will read zero.

2. Move the highlight bar to the

TARGET GUIDE VANE POSITION

line and press the

SELECT softkey.

Do not permit water or brine that is warmer than 110 F (43 C) to flow through the
cooler or condenser. Refrigerant overpressure may discharge through the relief
devices and result in the loss of refrigerant charge.