Input the Design Set Points

Access the LID set point screen and view/modify the base demand limit set point, and

either

the LCW set point

or

the ECW set point. The PIC can control a set point to either the leaving or

entering chilled water. This control method is set in the Equipment Configuration table, Config

table.

Input the Local Occupied Schedule (OCCPC01S)

Access the schedule OCCPC01S screen on the LID and set up the occupied time schedule

per the customer’s requirements. If no schedule is available, the default is factory set for 24

hours occupied 7 days per week including holidays.

For more information about how to set up a time schedule, see the

Controls

section.

The CCN Occupied Schedule (OCCPC03S) should be configured if a CCN system is being

installed or if a secondary time schedule is needed.

The Ice Build Occupied Schedule (OCCPC02S) should be configured for Ice Build

applications.