power the heater and the control circuit. This set up allows the heater to energize when the

main motor circuit breaker is off for service work or extended shutdowns. The oil heater relay

status can be viewed on the Status02 screen on the LID. Oil sump temperature can be viewed

on the LID default screen.

Software Version

The software version will always be labeled on the PSIO module, and on the back side of the

LID module. On both the Controller ID and LID ID display screens, the software version number

will also appear.

Set Up Machine Control Configuration

As configuration of the 17/19EX unit is performed, write down all configuration settings. A

log, such as the one shown in

Initial Start-Up Checklist

, provides a convenient list for con-

figuration values.

Do not operate the machine before the control configurations have been checked
and a Control Test has been satisfactorily completed. Protection by safety con-
trols cannot be assumed until all control configurations have been confirmed.

WARNING

!

WARNING