J. out-of-range sensor failures – Carrier 17/19EX User Manual

Page 320

Advertising
background image

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
J. Out-of-Range Sensor Failures

Primary Message

Secondary Message

Alarm Message/Primary
Cause

Additional Cause/
Remedy

Sensor Fault

Leaving CHW Tempera-
ture

Sensor Fault: Check leaving CHW
sensor.

See
sensor test procedure
and check sensors for
proper operation and
wiring.

Sensor Fault

Entering CHW Tempera-
ture

Sensor Fault: Check entering
CHW sensor.

Sensor Fault

Condenser Pressure

Sensor Fault: Check condenser
pressure transducer.

Sensor Fault

Evaporator Pressure

Sensor Fault: Check evaporator
pressure transducer.

Sensor Fault

Bearing Temperature

Sensor Fault: Check bearing tem-
perature sensor.

Sensor Fault

Motor Winding Temp

Sensor Fault: Check motor tem-
perature sensor.

Sensor Fault

Discharge Temperature

Sensor Fault: Check discharge
temperature sensor.

Sensor Fault

Oil Sump Temperature

Sensor Fault: Check oil sump tem-
perature sensor.

Sensor Fault

Oil Pressure Transducer

Sensor Fault: Check oil pressure
transducer.

Advertising