Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
L. Machine Alerts

Primary
Message

Secondary
Message

Alarm Message/
Primary Cause

Additional Cause/Remedy

Recycle Alert

High Amps at Shut-
down

High Amps at Recycle:
Check guide vane
drive.

Check that guide vanes are closing.
Check motor amps correction calibration is
correct. Check actuator for proper opera-
tion.

Sensor Fault
Alert

Leaving Cond Water
Temp

Sensor Fault: Check
leaving condenser
water sensor.

Check sensor. See sensor test procedure.

Sensor Fault
Alert

Entering Cond Water
Temp

Sensor Fault: Check
entering condenser
water sensor.

Low Oil
Pressure Alert

Check Oil Filter

Low Oil Pessure Alert:
Check oil.

Check oil filter. Check for improper oil level
or temperature.

AutoRestart
Pending

Power Loss

V P Power Loss:
Check voltage supply.

Check power supply if there are excessive
compressor starts occurring.

AutoRestart
Pending

Low Line Voltage

V P [VALUE] exceeded
limit of [LIMIT]*. Check
voltage supply.

AutoRestart
Pending

High Line Voltage

V P [VALUE] exceeded
limit of [LIMIT]*. Check
voltage supply.

Sensor Alert

High Discharge Temp

CMPD [VALUE]
exceeded limit of
[LIMIT]*. Check dis-
charge temperature.

Discharge temperature exceeded the alert
threshold. Check entering condenser
water temperature.

Sensor Alert

High Bearing Temper-
ature

MTRB [VALUE]
exceeded limit of
[LIMIT]*. Check thrust
bearing temperature.

Thrust bearing temperature exceeded the
alert threshold. Check for closed valves,
improper oil level or temperatures.

Condenser
Pressure Alert

Pump Relay Energized

CRP High Condenser
Pressure [LIMIT]*.
Pump energized to
reduce pressure.

Check ambient conditions. Check con-
denser pressure for accuracy.