Pack relay board, Input modules, Oil heater contactor (1c) – Carrier 17/19EX User Manual

Page 55: Oil pump contactor (2c)

Advertising
background image

6-Pack Relay Board

This device is a cluster of 6 pilot relays located in the control center. It is energized by the

PSIO for the oil pump, oil heater, alarm, optional hot gas bypass relay, and motor cooling

solenoid (19EX machines) on auxiliary oil pump (17EX machines).

8-Input Modules

One optional module is factory installed in the control center panel when ordered. There can

be up to 2 of these modules per chiller with 8 spare inputs each. They are used whenever

chilled water reset, demand reset, or reading a spare sensor is required. The sensors or 4 to

20 mA signals are field-installed.

The spare temperature sensors must have the same temperature/resistance curve as the

other temperature sensors on this unit. These sensors are rated 5,000 ohm at 75 F (25 C).

Oil Heater Contactor (1C)

This contactor is located in the power panel and operates the heater at 115 v. It is controlled

by the PIC to maintain oil temperature during machine shutdown.

Oil Pump Contactor (2C)

This contactor is located in the power panel. It operates all 200 to 575-v oil pumps. The PIC

energizes the contactor to turn on the oil pump as necessary.