I. normal run overrides active (alerts) – Carrier 17/19EX User Manual

Page 319

Advertising
background image

* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected

by the operator as an override, alert, or alarm contition. [VALUE] is the actual temperature, pressure,

voltage, etc., at which the control tripped.

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
I. Normal Run Overrides Active (Alerts)

Primary Message

Secondary Message

Alarm Message/Primary
Cause

Additional Cause/
Remedy

Run Capacity
Limited

High Condenser Pres-
sure

CRP [VALUE] exceeded limit of
[LIMIT]*. Condenser pressure
override.

See Capacity Over-
rides,

Table 4

. Correct

operating condition,
modify setpoint, or
release override.

Run Capacity
Limited

High Motor Temperature

MTRW [VALUE] exceeded limit of
[LIMIT]*. Motor temperature over-
ride.

Run Capacity
Limited

Low Evap Refrig Temp

ERT [VALUE] exceeded limit of
[LIMIT]*. Check refrigerant charge
level.

Run Capacity
Limited

High Compressor Lift

Surge Prevention Override; lift too
high for compressor.

Run Capacity
Limited

Manual Guide Vane Tar-
get

GV TRG Run Capacity Limited:
Manual Guide Vane Target.