Carrier 17/19EX User Manual

Page 94

Advertising
background image

Points, (T1/P1;T2/P2). These points have default settings as defined on the Service1 table, or

on

Table 4

. These settings and the algorithm function are graphically displayed in

Figure 21

and

Figure 22

. The 2 sets of load points on this graph (default settings are shown) describe a line

which the algorithm uses to determine the maximum lift of the compressor. Whenever the actual

differential pressure between the cooler and condenser, and the temperature difference

between the entering and leaving chilled water are above the line on the graph (as defined by

the MINIMUM and MAXIMUM Load Points) the algorithm will go into a corrective action mode. If

the actual values are below the line, the algorithm takes no action. Modification of the default

set points of the MINIMUM and MAXIMUM load points is described in the

Input Service

Configurations

section.

Corrective action can be taken by making one of 2 choices. If a hot gas bypass line is

present, and the hot gas is configured on the Service1 table, then the hot gas bypass valve can

be energized. If a hot gas bypass if not present, then the action taken is to hold the guide vanes.

See

Table 4

, Capacity Overrides. Both of these corrective actions will reduce the lift

experienced by the compressor and help to prevent a surge condition. Surge is a condition

when the lift becomes so high that the gas flow across the impeller reverses. This condition can

eventually cause machine damage. The surge prevention algorithm is intended to notify the

operator that machine operating conditions are marginal, and to take action, such as lowering

entering condenser water temperature, to help prevent machine damage.

Advertising