Whenever the motor current demand limit set point is reached, it activates a capacity

override, again with a 2-step process. Exceeding 110% of the rated load amps for more than 30

seconds will initiate a safety shutdown.

The compressor high lift (surge prevention) set point will cause a capacity override as well.

When the surge prevention set point is reached, the controller normally will only hold the guide

vanes from opening. If so equipped, the hot gas bypass valve will open instead of holding the

vanes.

High Discharge Temperature Control

If the discharge temperature increases above 200 F (93 C), the guide vanes are

proportionally opened to increase gas flow through the compressor. If the leaving chilled water

temperature drops 5° F (2.8° C) below the control point temperature, machine will enter the

recycle mode.

Click here for Table 3 — Protective Safety Limits and Control Settings

Click here for Table 4 — Capacity Overrides