SERVICE2 TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

RESET 20 mA Power Source

0/1

0 = EXTERNAL, 1 = INTERNAL

0

DEMAND 20 mA Power Source

0/1

0 = EXTERNAL, 1 = INTERNAL

0

CHWS Temp Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

CHWS Temp Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

CHWR Temp Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

CHWR Temp Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

Reset Temp Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Reset Temp Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

Spare Temp 1 Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Spare Temp 1 Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

Spare Temp 2 Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Spare Temp 2 Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

Spare Temp 3 Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Spare Temp 3 Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

SPARE 1 20 mA Power Source

0/1

0 = EXTERNAL, 1 = INTERNAL

0

SPARE 2 20 mA Power Source

0/1

0 = EXTERNAL, 1 = INTERNAL

0

Spare Temp 4 Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Spare Temp 4 Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

Spare Temp 5 Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Spare Temp 5 Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

Spare Temp 6 Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Spare Temp 6 Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

Spare Temp 7 Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Spare Temp 7 Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

Spare Temp 8 Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Spare Temp 8 Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)

Spare Temp 9 Enable

0 to 4

0 = DISABLE, 1 = HIGH ALERT, 2 = LOW ALERT,
3 = HIGH ALARM, 4 = LOW ALARM

0

Spare Temp 9 Alert

–40 to 245
(–40 to 118)

DEG F
(DEG C)

245

(118)