SERVICE1 TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Motor Temp Override

150 to 200

(66 to 93)

DEG F
(DEG C)

200

(93)

Cond Pressure Override

90 to 200 (620 to 1379)

psig
(kPa)

125 (862)

Refrig Override Delta T

2 to 5

(1 to 3)

DEG F
(DEG C)

3

(1.6)

Chilled Medium

Water/Brine

Water

Brine Refrig Trippoint

8 to 40

(–13.3 to 4)

DEG F
(DEG C)

33

(1)

Compr Discharge Alert

125 to 200

(52 to 93)

DEG F
(DEG C)

200

(93)

Bearing Temp Alert

165 to 210

(74 to 99)

DEG F
(DEG C)

210

(99)

Water Flow Verify Time

0.5 to 5

MIN

5

Oil Press Verify Time

15 to 300

SEC

15

Water/Brine Deadband

0.5 to 2.0

(0.3 to 1.1)

DEG F
(DEG C)

1.0

(0.6)

Recycle Restart Delta T

2.0 to 10

(1.1 to 5.5)

DEG F
(DEG C)

5

(2.8)

Recycle Shutdown Delta T

0.5 to 4.0

(0.27 to 2.2)

DEG F
(DEG C)

1.0

(0.6)

Surge Limit/HGBP Option
Surge=0/HGBP=1

0/1

0

Surge/HGBP Delta T1

0.5 to 15

(0.3 to 8.3)

DEG F
(DEG C)

1.5

(0.8)

Surge/HGBP Delta P1

30 to 170 (206 to 1172)

psi
(kPa)

50 (345)

Surge/HGBP Delta T2

0.5 to 15.0

(0.3 to 8.3)

DEG F
(DEG C)

10

(5.6)

Surge/HGBP Delta P2

30 to 170 (206 to 1172)

psi
(kPa)

85 (586)

Surge/HGBP Deadband

1 to 3

(0.6 to 1.6)

DEG F
(DEG C)

1

(0.6)

Surge Delta Percent Amps

10 to 50

%

25

Surge Time Period

1 to 5

MIN

2

Demand Limit Source
Amps=0/Load=1

0/1

0

Amps Correction Factor

1 to 8

3

CL-7