Example 11 — maintenance (maint02) display screen – Carrier 17/19EX User Manual

Page 297

Advertising
background image

Example 11 — Maintenance (Maint02) Display Screen

To access this display from the LID default screen:

1. Press MENU.

2. Press SERVICE.

3. Scroll down to highlight CONTROL ALGORITHM STATUS.

4. Press SELECT.

5. Scroll down to highlight MAINT02.

6. Press SELECT.

Note: Overriding is not supported on this maintenance screen. Active overrides show the associated point in

alert (*). Only values with capital letter reference point names are variables available for read opera-

tion.

† Information is applicable to hermetic machines only.

Table 2, Example 11 — Maintenance (Maint02) Display Screen

Description

Range/Status

Units

Reference
Point Name

OVERRIDE/ALERT STATUS
MOTOR WINDING TEMP

Override Threshold
CONDENSER PRESSURE
Override Threshold
EVAPORATOR REFRIG TEMP
Override Threshold
DISCHARGE TEMPERATURE
Alert Threshold
BEARING TEMPERATURE
Alert Threshold

–40-245 (–40-118)
150-200 (66-93)
-6.7-420 (-42-2896)
90-245 (621-1689)
–40-245 (–40-118)
2-45 (1-7.2)
–40-245 (–40-118)
125-200 (52-93)
–40-245 (–40-118)
175-185 (79-85)

DEG F (DEG C)
DEG F (DEG C)
PSI (kPa)
PSI (kPa)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)

MTRW
mt over
CRP
cp over
ERT
rt over
CMPD
cd alert
MTRB
tb alert

Advertising