Flow Switches (Field Supplied)

Operate water pumps with machine off. Manually reduce water flow and observe switch for proper cutout.

Safety shutdown occurs when cutout time exceeds 3 seconds.

Starter Acceleration Time
(Determined by inrush
current going below 100%
compressor motor load)

>

45 seconds

For machines with reduced voltage
mechanical and solid-state starters

>

10 seconds

For machines with full voltage starters
(Configured on Service1 table)

Starter Transition

>

75 seconds

Reduced voltage starters only

Condenser Freeze
Protection

Energizes condenser pump relay if
condenser refrigerant temperature or
condenser entering water tempera-
ture is below the configured con-
denser freeze point temperature.
Deenergizes when the temperature is
5 F (3 C) above condenser freeze
point temperature.

CONDENSER FREEZE POINT config-
ured in Service01 table with a default
seting of 34 F (1 C).

Impeller Clearance

Displacement switch open

Thrust movement excessive

Motor Leak Detector*

Water from motor cooling is leaking

Water sensors are installed only on
open-drive motors that use water cool-
ing. (Totally enclosed, water-to-air
cooled [TEWAC] motors)

Table 3 — Protective Safety Limits and Control Settings (Continued)

Monitored Parameter

Limit

Applicable Comments

Carrier Part No. HK06ZC033

* Applicable to open drive machines only.

Carrier Part No. HK06ZC001

Note: Dimensions in parenthesis are

in millimeters

NO ADJUSTMENTS ARE TO BE MADE ON THIS
SETSCREW! (FACTORY ADJUSTED ONLY)