Pic system functions, Capacity control, Entering chilled water control – Carrier 17/19EX User Manual

Page 74

Advertising
background image

PIC System Functions

Note: Throughout this manual, words printed in capital letters and italics are values that may be

viewed on the LID. See Table 2 for examples of LID screens. Point names are listed in

the Description column. An overview of LID operation and menus is given in

Figure 14

,

Figure 15

,

Figure 16

,

Figure 17

,

Figure 18

,

Figure 19

, and

Figure 20

.

Capacity Control

The PIC controls the machine capacity by modulating the inlet guide vanes in response to

chilled water temperature changes away from the

CONTROL POINT

. The

CONTROL POINT

may be changed by a CCN network device, or is determined by the PIC adding any active

chilled water reset to the chilled water

SET POINT

. The PIC uses the

PROPORTIONAL INC

(Increase) BAND, PROPORTIONAL DEC (Decrease) BAND

, and the

PROPORTIONAL ECW

(Entering Chilled Water) GAIN

to determine how fast or slow to respond.

CONTROL POINT

may be viewed/overridden on the Status table, Status01 selection.

Entering Chilled Water Control

If this option is enabled, the PIC uses

ENTERING CHILLED WATER

temperature to

modulate the vanes instead of

LEAVING CHILLED WATER

temperature.

ENTERING CHILLED

WATER

control option may be viewed/modified on the Equipment Configuration table, Config

table.