INSPECT WIRING AND RECORD ELECTRICAL DATA:

RATINGS:

Motor Voltage

Motor(s) Amps

Oil Pump Voltage

Starter Amps

Line Voltages:

Motor

Oil Pump

Controls/Oil Heater

STARTER CHECKOUT:

Check continuity T1 to T1, etc. (Motor to starter, disconnect motor leads T4, T5, T6.) Do not megohm test solid-state starters,
disconnect leads to motor and megger the leads.

MEGGER MOTOR

‘‘PHASE TO PHASE’’

‘‘PHASE TO GROUND’’

T1-T2

T1-T3

T2-T3

T1-G

T2-G

T3-G

10-Second Readings:
60-Second Readings:
Polarization Ratio:

STARTER:

Electro-Mechanical

Solid-State

Motor Load Current Transformer Ratio

:

Signal Resistor Size

Ohms

Transition Timer Time

Seconds

Check Magnetic Overloads

Add Dash Pot Oil

Yes

No

Solid-State Overloads

Yes

No

Solid State Starter:

Torque Setting

O’Clock

Ramp Setting

Seconds

OPEN-DRIVE MOTOR BEARINGS: Added Oil to Proper Level

Yes

CONTROLS: SAFETY, OPERATING, ETC.

Perform Controls Test (Yes/No)

PIC CAUTION

COMPRESSOR MOTOR AND CONTROL PANEL MUST BE PROPERLY AND INDIVIDUALLY CON-
NECTED BACK TO THE EARTH GROUND IN THE STARTER. (IN ACCORDANCE WITH BULLETIN
C-8912).

Yes

RUN MACHINE:

Do these safeties shut down machine?

Condenser Water Flow Switch

Yes

No

Chilled Water Flow Switch

Yes

No

Pump Interlocks

Yes

No

INITIAL START:

Line Up All Valves in Accordance With Instruction Manual:

Start Water Pumps and Establish Water Flow

Oil Level OK and Oil Temperature OK

Check Oil Pump Rotation-Pressure

Check Compressor Motor Rotation (Motor End Sight Glass) and Record:

Clockwise

Restart Compressor, Bring Up To Speed. Shut Down. Any Abnormal Coastdown Noise?

Yes*

No

*If yes determine cause.

START MACHINE AND OPERATE. COMPLETE THE FOLLOWING:

A: Trim Charge and Record Under Charge Refrigerant Section on page 57.
B: Complete Any Remaining Control Calibration and Record Under Controls Section (pages 12-45).
C: Take At Least 2 Sets of Operational Log Readings and Record.
E: After Machine Has Been Successfully Run and Set Up, Shut Down and Mark Shutdown Oil and Refrigerant Levels.

F: Give Operating Instructions to Owner’s Operating Personnel.

Hours Given:

Hours

G: Perform Hot Alignment (Open Drive Machines Only)

SIGNATURES:

DATE

CARRIER

CUSTOMER REPRESENTATIVE

TECHNICIAN

DATE

CL-2