Certain conditions during shutdown will change this sequence:

if the

COMPRESSOR MOTOR LOAD

is greater than 10% after shutdown, or the

starter contacts remain energized, the oil pump and chilled water pump remain ener-
gized and the alarm is displayed

if the

ENTERING CONDENSER WATER

temperature is greater than 115 F (46 C) at

shutdown, the condenser pump will be deenergized after the 1CR compressor start
relay

if the machine shuts down due to low refrigerant temperature, the chilled water pump
will stay running until the

LEAVING CHILLED WATER

is greater than

CONTROL

POINT

, plus 5° F (3° C)

Automatic Soft Stop Amps Threshold

The SOFT STOP AMPS THRESHOLD closes the guide vanes of the compressor

automatically when a non-recycle, non-alarm stop signal occurs before the compressor motor is

deenergized.

If the STOP button is pressed, the guide vanes close to a preset amperage percent or until

the guide vane is less than 2% open. The compressor will then shut off.

If the machine enters an alarm state or if the compressor enters a RECYCLE mode, the

compressor will be deenergized immediately.

To activate SOFT STOP AMPS THRESHOLD, view the bottom of Service1 table. Set the

SOFT STOP AMPS THRESHOLD value to the percentage amps at which the motor will shut

down. The default setting is 100% amps (no Soft Stop).