B. timing out or timed out – Carrier 17/19EX User Manual

Page 311

Advertising
background image

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
B. Timing Out or Timed Out

Primary Message

Secondary Message

Probable Cause/Remedy

Ready To Start In XX
Min

Unoccupied Mode

Time schedule for PIC is unoccupied. Machines will
start only when occupied.

Ready To Start In XX
Min

Remote Contacts Open

Remote contacts have stopped machine. Close con-
tacts to start.

Ready To Start In XX
Min

Stop Command In Effect

Chiller START/STOP on Status01 manually forced to
stop. Release value to start.

Ready To Start In XX
Min

Recycle Restart Pending

Machine in recycle mode.

Ready To Start

Unoccupied Mode

Time schedule for PIC is UNOCCUPIED. Machine will
start when occupied. Make sure the time and date have
been set on the Service menu.

Ready To Start

Remote Contacts Open

Remote contacts have stopped machine. Close con-
tacts to start.

Ready To Start

Stop Command In Effect

Chiller START/STOP on Status01 manually forced to
stop. Release value to start.

Ready To Start In XX
Min

Remote Contacts Closed

Machine timer counting down unit. Ready for start.

Ready To Start In XX
Min

Occupied Mode

Machine timer counting down unit. Ready for start.

Ready To Start

Remote Contacts Closed

Machine timers complete, unit start will commence.

Ready To Start

Occupied Mode

Machine timers complete, unit start will commence.

Startup Inhibited

Loadshed In Effect

CCN loadshed module commanding chiller to stop.

Ready To Start In XX
Min

Start Command In Effect

Chiller START/STOP on Status01 has been manually
forced to start. Machine will start regardless of time
schedule or remote contact status.

Advertising