Carrier 17/19EX User Manual

Page 42

Advertising
background image

Compression raises the refrigerant temperature above that of the water flowing through the

condenser tubes. When the warm (typically 98 to 102 F [37 to 40 C]) refrigerant vapor comes

into contact with the condenser tubes, the relatively cool condensing water (typically 85 to 95 F

[29 to 35 C]) removes some of the heat and the vapor condenses into a liquid.

The liquid refrigerant passes through an orifice into the FLASC chamber. Because the

coolest condenser water is flowing through the FLASC, it is at a lower pressure and part of the

entering liquid refrigerant will flash to vapor, thereby cooling the remaining liquid. The vapor is

then recondensed by the condenser water flowing through the FLASC chamber.

The subcooled liquid refrigerant drains into a high-side valve chamber which meters the

refrigerant liquid into a flash economizer chamber. Pressure in this chamber is intermediate

between condenser and cooler pressures. At this lower pressure, some of the liquid refrigerant

flashes to gas, further cooling the remaining liquid. The flash gas, having absorbed heat, is

returned directly to the compressor second stage. Here it is mixed with discharge gas that is

already compressed by the first-stage impeller. Since the flash gas has to pass through only

half the compression cycle, to reach condenser pressure, there is a savings in power.

The cooled liquid refrigerant in the economizer is metered through the low-side valve

chamber into the cooler. Because pressure in the cooler is lower than economizer pressure,

some of the liquid flashes and cools the remainder to evaporator (cooler) temperature. The

cycle is now complete.

Advertising