Machine Dehydration

Dehydration is recommended if the machine has been open for a considerable period of

time, if the machine is known to contain moisture, or if there has been a complete loss of

machine holding charge or refrigerant pressure.

Click here for Table 5A — HFC-134a Pressure — Temperature (F)

Click here for Figure 28 — 17/19EX Leak Test Procedures

Click here for Table 5B — HFC-134a Pressure — Temperature (C)

Do not start or megohm test the compressor motor or oil pump motor, even for a
rotation check, if the machine is under dehydration vacuum. Insulation break-
down and severe damage may result.