Notes on Module Operation

1. The machine operator monitors and modifies configurations in the microprocessor through

the 4 softkeys and the LID. Communication with the LID and the PSIO is accomplished

through the CCN bus. The communication between the PSIO, SMM, and both 8-input

modules is accomplished through the sensor bus, which is a 3-wire cable.

On sensor bus terminal strips, Terminal 1 of PSIO module is connected to Terminal 1 of

each of the other modules. Terminals 2 and 3 are connected in the same manner. See

Figure 49

,

Figure 50

,

Figure 51

,

Figure 52

, and

Figure 53

. If a Terminal 2 wire is connected

to Terminal 1, the system does not work.

2. If a green LED is solid on, check communication wiring. If a green LED is off, check the red

LED operation. If the red LED is normal, check the module address switches (

Figure 49

,

Figure 50

,

Figure 51

,

Figure 52

, and

Figure 53

). Proper addresses are:

Module

Address

SW1

SW2

SMM (Starter Management Module)

8-input Options Module 1
8-input Options Module 2

3
6
7

2
4
2