Prepare the Machine for Start-Up

Follow the steps described in the

Initial Start-Up

section.

To Start the Machine

1. Start the water pumps, if they are not automatic.

2. On the LID default screen, press the LOCAL or CCN softkey to start the system. If the

machine is in the OCCUPIED mode, and the 3- and 15-minute start timers have expired,

the start sequence will start. Follow the procedure described in the

Start-Up/Shutdown/

Recycle

section.

Check the Running System

After the compressor starts, the operator should monitor the LID display and observe the

parameters for normal operating conditions:

1. The oil reservoir temperature should be above 150 F (66 C) or refrigerant temperature plus

70° F (38° C) during shutdown, and above 125 F (52 C) during compressor operation.

2. The bearing oil temperature accessed on the Status01 LID screen should be 150 to 200 F

(65 to 93 C). If the bearing temperature reads more than 210 F (99 C) with the oil pump

running, stop the machine and determine the cause of the high temperature.

Do not restart

the machine until corrected.

3. The oil level should be visible in the lower sight glass when the compressor is running.