Example 2, Status02 display screen, Example 2 — status02 display screen – Carrier 17/19EX User Manual

Page 286

Advertising
background image

Example 2 — Status02 Display Screen

To access this display from the LID default screen:

1. Press MENU.

2. Press STATUS.

3. Scroll down to highlight STATUS02.

4. Press SELECT.

Note: All values are variables available for read operation to a CCN. Descriptions shown with (*) support

write operations from the LID only.

† Information is applicable to hermetic machines only.

** Information is applicable to open-drive machines only.

Table 2, Example 2 — Status02 Display Screen

Description

Point Type

Units

Reference Point
Name (Alarm
History)

Input

Output

Hot Gas Bypass Relay
*Chilled Water Pump
Chilled Water Flow
*Condenser Water Pump
Condenser Water Flow
Compressor Start Relay
Compressor Start Contact
Compressor Run Contact
Starter Fault Contact
Pressure Trip Contact
Single Cycle Dropout
Oil Pump Relay
Oil Heater Relay
Motor Cooling Relay

Auxiliary Oil Pump Relay**
*Tower Fan Relay
Compr. Shunt Trip Relay
Alarm Relay
Spare Prot Limit Input

X

X

X
X
X
X
X

X

X
X

X

X

X
X
X
X
X
X
X

OFF/ON
OFF/ON
NO/YES
OFF/ON
NO/YES
OFF/ON
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
NORMAL/ALARM
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
NORMAL/ALARM
ALARM/NORMAL

HGBR
CHWP
EVFL
CDP
CDFL
CMPR
1CR AUX
RUN AUX
STR FLT
PRS TRIP
V1 CYCLE
OILR
OILH
MTRC
AUXOILR
TFR
TRIPR
ALM
SPR PL