Condenser pump control, Condenser freeze prevention – Carrier 17/19EX User Manual

Page 88

Advertising
background image

Condenser Pump Control

The machine will monitor the

CONDENSER PRESSURE

and may turn on this pump if the

pressure becomes too high whenever the compressor is shut down.

CONDENSER

PRESSURE OVERRIDE

is used to determine this pressure point. This value is found on the

Equipment Service1 LID table and has a default value (

Table 4

). If the

CONDENSER

PRESSURE

is greater than or equal to the

CONDENSER PRESSURE OVERRIDE

, and the

ENTERING CONDENSER WATER TEMP (Temperature)

is less than 115 F (46 C), then the

condenser pump will energize to try to decrease the pressure. The pump will turn off when the

condenser pressure is less than the pressure override less 5 psi (34 kPa), or the

CONDENSER

REFRIG (Refrigerant) TEMP

is within 3° F (2° C) of the

ENTERING CONDENSER WATER

temperature.

Condenser Freeze Prevention

This control algorithm helps prevent condenser tube freeze-up by energizing the condenser

pump relay. If the pump is controlled by the PIC, starting the pump will help prevent the water in

the condenser from freezing. Condenser freeze prevention can occur whenever the machine is

not running except when it is either actively in pumpdown or in Pumpdown Lockout with the

freeze prevention disabled (refer to Control Test table, Pumpdown/Terminate Lockout tables).

When the

CONDENSER REFRIG TEMP

is less than or equal to the

CONDENSER FREEZE

POINT

, or the

ENTERING CONDENSER WATER

temperature is less than or equal to the