If, after configuring a value for these points, surge prevention is operating too soon or too late

for conditions, these parameters should be changed by the operator.

Example of configuration: Machine operating parameters

Refrigerant used: HFC-134a

Estimated Minimum Load Conditions:

44 F (6.7 C) LCW

45.5 F (7.5 C) EWC

43 F (6.1 C) Suction Temperature

70 F (21.1 C) Condensing Temperature

Estimated Maximum Load Conditions:

44 F (6.7 C) LCW

54 F (12.2 C) ECW

42 F (5.6 C) Suction Temperature

98 F (36.7 C) Condensing Temperature

Calculate Maximum Load

To calculate maximum load points, use design load condition data. If the machine full load

cooler temperature difference is more than 15° F (8.3° C), estimate the refrigerant suction and

condensing temperatures at this difference. Use the proper saturated pressure and temperature

for the particular refrigerant used.