Example 5, Configuration (config) display scree, Example 5 — configuration (config) display screen – Carrier 17/19EX User Manual

Page 289: Equipment configuration

Advertising
background image

Example 5 — Configuration (Config) Display Screen

To access this display from the LID default screen:

1. Press MENU.

2. Press SERVICE.

3. Scroll down to highlight EQUIPMENT CONFIGURATION.

4. Press SELECT.

5. Scroll down to highlight CONFIG.

6. Press SELECT.

Note:

= delta degrees.

Table 2, Example 5 — Configuration (Config) Display Screen

Description

Configurable
Range

Units

Reference
Point Name

Default
Value

RESET TYPE 1
Degrees Reset at 20 mA
RESET TYPE 2
Remote Temp (No Reset)
Remote Temp (Full Reset)
Degrees Reset
RESET TYPE 3
CHW Delta T (No Reset)
CHW Delta T (Full Reset)
Degrees Reset
Select/Enable Reset Type
ECW CONTROL OPTION
Demand Limit At 20 mA
20mA Demand Limit Option
Auto Restart Option
Remote Contacts Option
Temp Pulldown Deg/Min
Load Pulldown %/Min
Select Ramp Type:

Temp = 0, Load = 1

Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
CCN Occupancy Config:

Schedule Number
Broadcast Option

ICE BUILD Option
ICE BUILD TERMINATION
0 =Temp, 1 =Contacts, 2 =Both
ICE BUILD Recycle Option

–30-30 (–17-17)

–40-245 (–40-118)
–40-245 (–40-118)
–30-30 (–17-17)

0-15 (0-8)
0-15 (0-8)
–30-30 (–17-17)
0-3
DISABLE/ENABLE
40-100
DISABLE/ENABLE
DISABLE/ENABLE
DISABLE/ENABLE
2-10
5-20
0/1

0-99
0-60
0-120

3-99
DISABLE/ENABLE
DISABLE/ENABLE

0-2
DISABLE/ENABLE

DEG F (DEG C)

DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)

DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)

%

%
MIN

deg 20mA

res rt1
res rt2
res rt

restd 1
restd 2
deg chw
res sel
ecw opt
dem 20ma
dem sel
astart
r contact
tmp ramp
kw ramp
ramp opt

ldsgrp
ldsdelta
maxldstm

occpcxxe
occbrcst
ibopt

ibterm
ibrecyc

10

(6

)

85 (29)
65 (18)
10

(6

)

10

(6

)

0

(0

)

5

(3

)

0
DISABLE
40
DISABLE
DISABLE
DISABLE
3
10
1

0
20
60

3
DISABLE
DISABLE

0
DISABLE