Carrier 17/19EX User Manual

Page 123

Advertising
background image

is an operator-configured function which defaults to 5° F (3° C). This value is viewed/modified

on the Service1 table. The compressor will restart when:

in LCW CONTROL the

LEAVING CHILLED WATER

temperature is greater than the

CONTROL POINT

plus the

RECYCLE RESTART DELTA T

; or

in ECW CONTROL, the

ENTERING CHILLED WATER

temperature is greater than

the

CONTROL POINT

plus the

RECYCLE RESTART DELTA T

Once these conditions are met, the compressor shall initiate a start-up, with a normal start-up

sequence.

An alert condition may be generated if 5 or more RECYCLE STARTUPs occur in less than 4

hours. This excessive recycling can reduce machine life. Compressor recycling due to

extremely low loads should be reduced. To reduce compressor recycling, use the time schedule

to shut the machine down during low load operation or increase the machine load by running

the fan systems. If the hot gas bypass is installed, adjust the values to ensure that hot gas is

energized during light load conditions. Increase the

RECYCLE RESTART DELTA T

on the

Service1 table to lengthen the time between restarts.

The machine should not be operated below design minimum load without a hot gas bypass

installed on the machine.