Check Insulation Resistance (Hermetic Motor)

Test the machine compressor motor and its power lead insulation resistance with a 500-v

insulation tester such as a megohmmeter. (Use a 5000-v tester for motors rated over 600 v.)

Factory-mounted starters do not require a megohm test.

1. Open the starter main disconnect switch and follow lockout/tagout rules.

2. With the tester connected to the motor leads, take 10-second and 60-second megohm

readings as follows:

6-Lead Motor — Tie all 6 leads together and test between the lead group and ground. Next

tie leads in pairs, 1 and 4, 2 and 5, and 3 and 6. Test between each pair while grounding the

third pair.

3-Lead Motor — Tie terminals 1, 2, and 3 together and test between the group and ground.

3. Divide the 60-second resistance reading by the 10-second reading. The ratio, or

polarization index, must be one or higher. Both the 10- and 60-second readings must be at

least 50 megohms.

CAUTION

CAUTION

!

If the motor starter is a solid-state starter, the motor leads must be disconnected
from the starter before an insulation test is performed. The voltage generated
from the tester can damage the starter solid-state components.