Table 13 — additional cooler weights, Table 13 – Carrier 17/19EX User Manual

Page 337

Advertising
background image

NIH — Nozzle-In-Head

* When using a machine configuration other than 2-pass, NIH waterboxes with 150 psig (1038 kPa)

covers, add the weights listed in this table to the appropriate weights in

Table 10

to obtain the correct

cooler weight.

Table 13 — Additional Cooler Weights*

Component

Waterbox
Type

Number
of
Passes

Design
Maximum
Water Pressure

Additional
Dry Weight

Additional
Water Weight

psig

kPa

lb

kg

lb

kg

Condenser

NIH

1, 3

150

1034

515

234

-

-

NIH

1, 3

300

2068

2941

1334

-

-

NIH

2

300

2068

2085

946

-

-

Marine

1, 3

150

1034

2100

953

5102

2314

Marine

2

150

1034

792

359

2551

1157

Marine

1, 3

300

2068

3844

1744

5102

2314

Marine

2

300

2068

2536

1150

2551

1157