Table 4, Capacity overrides, Table 4 — capacity overrides – Carrier 17/19EX User Manual

Page 302

Advertising
background image

Legend
P1 — Minimum Pressure Load

T1 — Minimum Temperature Load

P2 — Maximum Pressure Load

T2 — Maximum Temperature Load

* Not available on open drive machines.

Table 4 — Capacity Overrides

Override
Capacity
Control

First Stage Setpoint

Second
Stage
Setpoint

Override
Termination

View/
Modify
on LID
Screen

Default Value

Configurable Range

Value

Value

High
Condenser
Pressure

Equip-
ment
Service1

125 psig (862 kPa)

90 to 200 psig
(620-1379 kPa)

>

Override Set

Point + 4 psid
(28 kPad)

<

Override

Set Point

High Motor
Temperature*

Equip-
ment
Service1

>

200 F (93.3 C)

150 to 200 F
(66 to 93 C)

>

Override Set

Point +10° F
(6° C)

<

Override

Set Point

Low
Refrigerant
Temperature
(Refrigerant
Override
Delta
Temperature)

Equip-
ment
Service1

<

3° F (1.6° C) (Above

Trippoint)

2° to 5° F
(1° to 3° C)

Trippoint +

Override

T –1° F

(0.56° C)

>

Trippoint +

Override

T +2° F

(1.2° C)

High
Compressor
LIft (Surge
Prevention)

Equip-
ment
Service1

Min: T1 – 1.5° F

(0.8° C)
P1 – 50 psid
(345 kPad)

Max: T2 – 10° F

(5.6° C)
P2 – 85 psid
(586 kPad)

0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to 1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to 1172 kPad)

None

Within Lift
Limits Plus
Surge/HGBP
Deadband
Setting

Manual Guide
Vane Target

Control
Algorithm
Maint01

Automatic

0 to 100%

None

Release of
Manual Con-
trol

Motor Load —
Active
Demand Limit

Status01

100%

40 to 100%

5% of Set

Point

2% Lower
Than Set
Point