Table 3 — Protective Safety Limits and Control Settings

Monitored Parameter

Limit

Applicable Comments

Temperature Sensors Out
Of Range

–40 to 245 F (–40 to 118.3 C)

Must be outside range for 2 seconds

Pressure Transducers Out
Of Range

0.08 to 0.98 Voltage Ratio

Must be outside range for 2 seconds.
Ratio = Input Voltage ÷ Voltage Refer-
ence

Compressor Discharge
Temperature

>

220 F (104.4 C)

Preset, alert setting configurable

Motor Winding Temperature

>

220 F (104.4 C)

Preset; alert setting configurable

Bearing Temperature

>

220 F (104.4 C)

Preset; alert setting configurable

Evaporator Refrigerant
Temperature (Temp
converted from Pressure
Reading)

<

33 F (for water chilling) (0.6° C)

Preset; configure chilled medium for
water (Service1 table)

<

Brine Refrigerant Trippoint (set point

adjustable from 0 to 40 F [–18 to 4 C]
for brine chilling)

Configure chilled medium for brine
(Service1 table). Adjust brine refrigerant
trippoint for proper cutout

Transducer Voltage

<

4.5 vdc

>

5.5 vdc

Preset (Read voltage at terminals 34
and 35 on PSIO module)

Condenser Pressure – Switch

– Control

>

218 psig ± 7 psig (1503 ± 48 kPa),

reset at 120 ± 10 (827 ± 69 kPa)

Preset

215 psig (1482 kPa)

Preset

Oil Pressure

– Switch

– Control

Cutout

<

11

psid (76 kPad) ± 1.5 psid

(10.3 kPad) Cut-in > 16.5 psid (114
kPad) ± 4 psid (27.5 kPad)

Preset, no calibration needed

Cutout

<

15 psid (103 kPad)

Alert < 18 psid (124 kPad)

Preset

Line Voltage —

High

Low

Single-cycle

>

110% for one minute

Preset, based on transformed line volt-
age to 24 vac rated-input to the Starter
Management Module. Also monitored at
PSIO power input.

<

90% for one minute and

85% for 3

seconds

<

50% for one cycle

Compressor Motor Load
(% Compressor Amps)

>

110% for 30 seconds

Preset

<

10% with compressor running

Preset

>

10% with compressor off

Preset