Example 4, Setpoint display screen, Example 4 — setpoint display screen – Carrier 17/19EX User Manual

Page 288

Advertising
background image

Example 4 — Setpoint Display Screen

To access this display from the LID default screen:

1. Press MENU.

2. Press SETPOINT.

Table 2, Example 4 — Setpoint Display Screen

Description

Configurable
Range

Units

Reference Point
Name

Default Value

Base Demand Limit
LCW Setpoint
ECW Setpoint
ICE BUILD Setpoint

40-100
20-120 (–6.7-48.9)
20-120 (–6.7-48.9)
20-60 (–6.7-15.6)

%
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)

DLM
lcw sp
ecw sp
ice sp

100
50.0 (10.0)
60.0 (15.6)
40.0 ( 4.4)