3. Press ENTER to override the automatic target. The screen will now read a value of zero,

and the word ‘‘SUPVSR!’’ will flash.

4. Press the SELECT softkey, and then press RELEASE softkey to release the vanes to

AUTOMATIC mode. After a few seconds the ‘‘SUPVSR!’’ will disappear.

Dry Run to Test Start-Up Sequence

1. Disengage the main motor disconnect on the starter front panel. This should only

disconnect the motor power. Power to the controls, oil pump, and starter control circuit

should still be energized.

2. Look at the default screen on the LID: the Status message in the upper left-hand corner will

show a ‘‘Manually Stopped’’ message. Press CCN or Local to start. If not, go to the

Schedule screen and override the schedule or change the occupied time. Press the LOCAL

softkey to begin the start-up sequences.

3. Check that chilled water and condenser water pumps energize.

4. Check that the oil pump starts and pressurizes the lubrication system. After the oil pump

has run about 15 seconds, the starter will be energized and go through its start-up

sequence.

5. Check the main contactor for proper operation.

6. The PIC will eventually show an alarm for motor amps not sensed. Reset this alarm and

continue with the initial start-up.