Shunt trip – Carrier 17/19EX User Manual

Page 80

Advertising
background image

If the controller initiates a safety shutdown, it displays the fault on the LID with a primary and

a secondary message, and energizes an alarm relay in the starter and blinks the alarm light on

the control center. The alarm is stored in memory and can be viewed in the PIC Alarm History

table along with a message for troubleshooting.

To give a better warning as to the operating condition of the machine, the operator also can

define alert limits on various monitored inputs. Safety contact and alert limits are defined in

Table 3

. Alarm and alert messages are listed in the

Troubleshooting Guide

section.

Shunt Trip

The optional shunt trip function of the PIC is a safety trip. The shunt trip is wired from an

output on the SMM to the motor circuit breaker. If the PIC tries to shut down the compressor

through normal shutdown procedure but is unsuccessful for 30 seconds, the shunt trip output is

energized and causes the circuit breaker to trip off. If ground fault protection has been applied

to the starter, the ground fault trip will also energize the shunt trip to trip the circuit breaker.

CAUTION

CAUTION

!

If compressor motor overload or ground fault occurs, check the motor for
grounded or open phases before attempting a restart.