Example 8 — Service2 Display Screen

To access this display from the LID default screen:

1. Press MENU.

2. Press SERVICE.

3. Scroll down to highlight EQUIPMENT SERVICE.

4. Press SELECT.

5. Scroll down to highlight SERVICE2.

6. Press SELECT.

Table 2, Example 8 — Service2 Display Screen

Description

Configurable
Range

Units

Reference
Point
Name

Default
Value

OPTIONS BOARD 1
20 mA POWER CONFIGURATION
External = 0, Internal = 1
RESET 20 mA Power Source
DEMAND 20 mA Power Source
SPARE ALERT ENABLE
Disable = 0, 1 = High Alert, 2 = Low Alert,
3 = High Alarm, 4 = Low Alarm
Temp = Alert Threshold
CHWS Temp Enable
CHWS Temp Alert
CHWR Temp Enable
CHWR Temp Alert
Reset Temp Enable
Reset Temp Alert
Spare Temp 1 Enable
Spare Temp 1 Alert
Spare Temp 2 Enable
Spare Temp 2 Alert
Spare Temp 3 Enable
Spare Temp 3 Alert

0, 1
0, 1

0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)

DEG F (DEG C)

DEG F (DEG C)

DEG F (DEG C)

DEG F (DEG C)

DEG F (DEG C)

DEG F (DEG C)

res 20 ma
dem 20 ma

chws en
chws al
chwr en
chwr al
rres en
rres al
spr1 en
spr1 al
spr2 en
spr2 al
spr3 en
spr3 al

0
0

0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)