Check pressure transducers, Pumpout system maintenance, Optional pumpout compressor oil charge – Carrier 17/19EX User Manual

Page 251

Advertising
background image

Check Pressure Transducers

Once a year, the pressure transducers should be checked against a pressure gage reading.

Check all three transducers: oil pressure, condenser pressure, cooler pressure.

Note the evaporator and condenser pressure readings on the Status01 screen on the LID.

Attach an accurate set of refrigeration gages to the cooler and condenser Schrader fittings.

Compare the two readings. If there is a difference in readings, the transducer can be calibrated,

as described in the

Troubleshooting Guide

section.

Pumpout System Maintenance

For compressor maintenance details, refer to the 06D, 07D Installation, Start-Up, and

Service Instructions.

Optional Pumpout Compressor Oil Charge

Use oil conforming to Carrier specifications for reciprocating compressor usage. Oil

requirements are as follows:

HFC-134a
ISO Viscosity ................................68
Carrier Part Number ..................PP23BZ103

The total oil charge, 4.5 pints (2.6 L), consists of 3.5 pints (2.0 L) for the compressor and one

additional pint (0.6 L) for the oil separator.

Advertising