Weekly Maintenance

Check the Lubrication System

Mark the oil level on the reservoir sight glass, and observe the level each week while the

machine is shut down.

If the level goes below the lower sight glass, the oil reclaim system will need to be checked

for proper operation. If additional oil is required, add oil as follows:

On hermetic machines, add oil through the oil drain charging valve (

Figure 3

, Item 26.) A

pump is required for adding oil against refrigerant pressure. On open-drive machines, oil may

be added through the oil drain and charging valve (

Figure 2

, Item 18) using a pump. However,

an oil charging elbow on the seal-oil return chamber (

Figure 6

) allows oil to be added without

pumping. The seal oil return pump automatically transfers the oil to the main oil reservoir. A

pump is required for adding oil against refrigerant pressure. The oil charge is approximately

15 gallons (57 L) for EX and FA (size 421-469) style compressors; 20 gallons (76 L) for EA (size

531-599) style compressors. The added oil

must

meet Carrier’s specifications. Refer to

Changing Oil Filter

and

Oil Changes

sections. Any additional oil that is added should be logged

by noting the amount and date. Any oil that is added due to oil loss that is not related to service

will eventually return to the sump, and must be removed when the level is high.

An oil heater is controlled by the PIC to maintain oil temperature above 150 F (65.5 C) or

refrigerant temperature plus 70° F (38.9° C) (see the

Controls

section) when the compressor is