Check Pumpout System Controls and Optional Pumpout Compressor

Controls include an on/off switch, a 3-amp fuse, the compressor overloads, an internal

thermostat, a compressor contactor, and a refrigerant high pressure cutout. The high pressure

cutout is factory set to open at 161 psig (1110 kPa) and reset at 130 psig (896 kPa). Check that

the water-cooled condenser has been connected. Loosen the compressor holddown bolts to

allow free spring travel. Open the compressor suction and discharge service valves. Check that

oil is visible in the compressor sight glass. Add oil if necessary.

See

Pumpout and Refrigerant Transfer Procedures

and

Pumpout System Maintenance

sections for details on transfer of refrigerant, oil specifications, etc.

High Altitude Locations

Recalibration of the pressure transducers will be necessary as the machine was initially

calibrated at sea level. Please see the calibration procedure in the

Troubleshooting Guide

section.