Faulted chiller operation – Carrier 17/19EX User Manual

Page 102

Advertising
background image

Lag Chiller Shutdown Requirements

The following conditions must be met in order for the lag chiller to be stopped.

1. Lead chiller COMPRESSOR MOTOR LOAD value is less than the lead chiller percent

capacity plus 15%.

Note: Lead chiller percent capacity = 100 – LAG PERCENT CAPACITY

The LAG PERCENT CAPACITY value is configured on the Lead/Lag Configuration screen.

2. The lead chiller chilled water temperature is less than the CONTROL POINT plus 1/2 of the

WATER/BRINE DEADBAND.

3. The configured LAG STOP TIMER entry has elapsed. The LAG STOP TIMER is started

when the CHILLED WATER TEMPERATURE is less than the CHILLED WATER

CONTROL POINT plus 1/2 of the WATER/BRINE DEADBAND and the lead chiller

COMPRESSOR MOTOR LOAD is less than the lead chiller percent capacity plus 15%. The

timer is ignored if the chilled water temperature reaches 3° F (1.67° C) below the

CONTROL POINT and the lead chiller COMPRESSOR MOTOR LOAD value is less than

the lead chiller percent capacity plus 15%.

Faulted Chiller Operation

If the lead chiller shuts down on an alarm (*) condition, it stops communication to the lag and

standby chillers. After 30 seconds, the lag chiller will now become the acting lead chiller and will

start and stop the standby chiller, if necessary.