Table 2 — LID Screens

Notes:

1. Only 12 lines of information appear on the LID screen at any given time. Press NEXT or PREVIOUS to

highlight a point or to view points below or above the current screen.

2. The LID may be configured in English or SI units, as required, through the LID configuration screen.

3. Data appearing in the Reference Point Names column is used for CCN operations only.

Example 1 — Status01 Display Screen

To access this display from the LID default screen:

1. Press MENU.

2. Press STATUS (STATUS01 will be highlighted).

3. Press SELECT.

Table 2, Example 1 — Status01 Display Screen

Description

Range

Units

Reference Point
Name (Alarm
History)

Control Mode
Run Status

Occupied ?
Alarm State
*Chiller Start/Stop
Base Demand Limit
*Active Demand Limit
Compressor Motor Load

Current
Amps

*Target Guide Vane Pos
Actual Guide Vane Pos
Water/Brine: Setpoint

* Control Point

Reset.Off.Local.CCN
Timeout.Recycle.Startup.

Ramping.Running.Demand.
Override.Shutdown.Abnormal.
Pumpdown

No/Yes

NORMAL/ALARM
STOP/START
40-100
40-100
0-999
0-999
0-9999
0-100
0-100
10-120 (–12.2-48.9)
10-120 (–12.2-48.9)

%
%
%
%
AMPS
%
%
DEG F (DEG C)
DEG F (DEG C)

MODE
STATUS

OCC

ALM
CHIL S S
DLM
DEM LIM
CA L
CA P
CA A
GV TRG
GV ACT
SP
LCW STPT