Attaching to other ccn modules – Carrier 17/19EX User Manual

Page 110

Advertising
background image

Attaching to Other CCN Modules

If the machine PSIO has been connected to a CCN Network or other PIC controlled chillers

through CCN wiring, the LID can be used to view or change parameters on the other controllers.

Other PIC machines can be viewed and set points changed (if the other unit is in CCN control),

if desired from this particular LID module.

To view the other devices, move to the ATTACH TO NETWORK DEVICE table. Move the

highlight bar to any device number. Press SELECT softkey to change the bus number and

address of the module to be viewed. Press EXIT softkey to move back to the ATTACH TO

NETWORK DEVICE table. If the module number is not valid, the ‘‘COMMUNICATION

FAILURE’’ message will show and a new address number should be entered or the wiring

checked. If the model is communicating properly, the ‘‘UPLOAD IN PROGRESS’’ message will

flash and the new module can now be viewed.

Whenever there is a question regarding which CCN module the LID is currently showing,

check the device name descriptor on the upper left hand corner of the LID screen. See

Figure 23

.

When the CCN device has been viewed, the ATTACH TO NETWORK DEVICE table should

now be used to attach to the PSIO that is on the machine. Move to the ATTACH TO NETWORK

DEVICE table and press the ATTACH softkey to upload the LOCAL device. The PSIO for the

19XT will now be uploaded.