Demand limiting, Machine timers – Carrier 17/19EX User Manual

Page 76

Advertising
background image

vane response to chilled water temperature below deadband plus control point. It can be

adjusted on the LID from a setting of 2 to 10, and the default setting is 6.0. Increasing either of

these settings will cause the vanes to respond slower than a lower setting.

The

PROPORTIONAL ECW GAIN

can be adjusted at the LID display from a setting of 1.0 to

3.0, with a default setting of 2.0. Increase this setting to increase guide vane response to a

change in entering chilled water temperature. The proportional bands and gain may be viewed/

modified on the Equipment Service3 table.

Demand Limiting

The PIC will respond to the

ACTIVE DEMAND LIMIT

set point by limiting the opening of the

guide vanes. It will compare the set point to either

COMPRESSOR MOTOR LOAD

or

COMPRESSOR MOTOR CURRENT

(percentage), depending on how the control is configured

for the

DEMAND LIMIT SOURCE

which is accessed on the SERVICE1 table. The default

setting is current limiting.

Machine Timers

The PIC maintains 2 runtime clocks, known as

COMPRESSOR ONTIME

and

SERVICE ON-

TIME. COMPRESSOR ONTIME

indicates the total lifetime compressor run hours. This timer

can register up to 500,000 hours before the clock turns back to zero. The

SERVICE ONTIME

is

a resettable timer that can be used to indicate the hours since the last service visit or any other

reason. The time can be changed through the LID to whatever value is desired. This timer can

register up to 32,767 hours before it rolls over to zero.

Advertising