Carrier 17/19EX User Manual

Page 294

Advertising
background image

Note: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp’’ thresh-

old for each point listed. If the ‘‘Enable’’ is set to 1, a value above the ‘‘Temp’’ threshold shall generate

an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold shall generate

an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled. If the “Enable” is set to 3, a

value above the “Temp” threshold will generate an alarm. If the “Enable” is set to 4, a value below the

“Temp” threshold will generate an alarm.

OPTIONS BOARD 2
20 mA POWER CONFIGURATION
External = 0, Internal = 1
SPARE 1 20 mA Power Source
SPARE 2 20 mA Power Source
SPARE ALERT ENABLE
Disable = 0, 1 = High Alert, 2 = Low Alert,
3 = High Alarm, 4 = Low Alarm
Temp = Alert Threshold
Spare Temp 4 Enable
Spare Temp 4 Alert
Spare Temp 5 Enable
Spare Temp 5 Alert
Spare Temp 6 Enable
Spare Temp 6 Alert
Spare Temp 7 Enable
Spare Temp 7 Alert
Spare Temp 8 Enable
Spare Temp 8 Alert
Spare Temp 9 Enable
Spare Temp 9 Alert

0, 1
0, 1

0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–40-118)
0-4
–40-245 (–0-118)
0-4
–40-245 (–40-118)

DEG F (DEG C)

DEG F (DEG C)

DEG F (DEG C)

DEG F (DEG C)

DEG F (DEG C)

DEG F (DEG C)

sp1 20 ma
sp2 20 ma

spr4 en
spr4 al
spr5 en
spr5 al
spr6 en
spr6 al
spr7 en
spr7 al
spr8 en
spr8 al
spr9 en
spr9 al

0
0

0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)
0
245 (118)

Table 2, Example 8 — Service2 Display Screen (Continued)

Description

Configurable
Range

Units

Reference
Point
Name

Default
Value