Logic Group (continued)

L190 [Stp Logic Time 0]
L192 [Stp Logic Time 2]
L194 [Stp Logic Time 4]
L196 [Stp Logic Time 6]

L191 [Stp Logic Time 1]
L193 [Stp Logic Time 3]
L195 [Stp Logic Time 5]
L197 [Stp Logic Time 7]

PowerFlex 525 only.

Sets the time to remain in each step if the corresponding command word is set to “Step based on time”.

Values

Default:

30.0 s

Min/Max:

0.0/999.9 s

Display:

0.1 s

PF 525

L200 [Step Units 0]
L204 [Step Units 2]
L208 [Step Units 4]
L212 [Step Units 6]

L202 [Step Units 1]
L206 [Step Units 3]
L210 [Step Units 5]
L214 [Step Units 7]

32 bit parameter.

PowerFlex 525 only.

Sets the position in user-defined units the drive must reach at each step.

Values

Default:

0

Min/Max:

0/6400

Display:

1

32

PF 525